VT8600 SeriesUser Interface Guide
22
Viconics Technologies Inc. 9245 Langelier Blvd. Saint-Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660
028-0441-00 www.viconics.com November 2014
© 2014 Viconics Technologies. All rights reserved.
CONFIGURATION PARAMETERS SCREEN 5/9
PARAMETER DETAILS SCREEN 5/9
Configuration Parameters Default Value Significance and Adjustments
Prop. band
Default value: 3.0
Proportional Band Setting
Adjusts proportional band used by the Terminal Equipment Controller PI control
loop.
Note: default value of 3.0 gives satisfactory operation in most normal installation
cases. The use of a superior proportional band different than the factory one is
normally warranted in applications where Terminal Equipment Controller location is
problematic and leads to unwanted cycling of the unit. A typical example is a wall
mounted unit where Terminal Equipment Controller is installed between return and
supply air feeds and is directly influenced by the supply air stream of unit.
Value Effective Proportional Band
Fahrenheit Celsius
3 3 1.2
4 4 1.7
5 5 2.2
6 6 2.8
7 7 3.3
8 8 3.9
9 9 5.0
10 10 5.6