VT8600 SeriesUser Interface Guide
18
Viconics Technologies Inc. 9245 Langelier Blvd. Saint-Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660
028-0441-00 www.viconics.com November 2014
© 2014 Viconics Technologies. All rights reserved.
PARAMETER DETAILS SCREEN 2/9
Configuration Parameters Default Value Significance and Adjustments
Standby mode
Default value: Abs
Standby Mode
Choose which standby setpoints are used for control.
Abs: absolute Standby entered values are used for standby mode.
Offset: relative Occupied setpoints +/- Standby diff. used for standby
mode.
Standby diff.
Default value: 2 °C ( 3 °F )
Standby Difference
When Standby mode is Relative, standby setpoints are calculated as:
Standby cool = Cool setpoint + Standby diff.
Standby heat = Heat setpoint - Standby diff.
Adjustable from 0.5 a 2.5 °C ( 1 - 5 °F )
Power-up delay
Default value: 10 seconds
On initial power up of the Terminal Equipment Controller (each time 24
Vac power supply is removed & re-applied) there is a delay before any
operation is authorized (fan, cooling or heating). This can be used to
sequence start up multiple units / Terminal Equipment Controller in one
location.
10 to 120 seconds