© 2015 Viconcis Technologies. All rights reserved.
Fan Coil Unit Controller SeriesApplication Guide
4
Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514 ) 321-4150
028-0444-01 www.viconics.com | sales@viconics.com February 2015
SC3500E5000
2 POSITION
COOLING VALVE
Cooling Coil
2 POSITION
HEATING VALVE
Heating Coil
Door Switch
SED-DOR-P-5000
Airflow Direction
Fan
VTR8300
Configuration
Parameter Name
Configuration Settings
Fan Menu L-M-H-A
Fan cont. heat. On
BI1 Motion NO or Motion NC (remote PIR sensor only)
BI2 Door Dry
Pulsed heating Off
Pipe no. 4
Seq. operation Ht - Cl
VTR83X0A5XXXB WITH SC3500E5000 RELAY AND VCM8000V5045P ZIGBEE PRO MODULE: HEATING/
COOLING 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND 2-POSITION VALVES WITH WIRELESS DOOR SWITCH
Onboard
PIR Sensor
AND / OR
OR*
Wired Remote
PIR Sensor
Wireless Remote
PIR Sensor
* Wired remote sensor cannot be used at the same time as wireless remote sensor(s).