Configuration properties (nci’s) Description
Parameter Variable Name Function
This configuration property defines the schedule for every day of
the week (from Monday to Sunday or from day 0 to day 6). This
nci is linked with the nvoEffectOccup variable.
2 or 4 events can entered depending on the nb_of_events
variable.
Starting and ending time are entered in minutes, e.i. 11:59 pm is
equal to 1439 minutes (23 hours * 60 min + 59 min)
Valid Range : 0 to 1439 minutes
Default values:
Sub Name Default Value
1 occupied_event_1 0
2 unoccupied_event_2 1439
3 occupied_event_3 0
Schedule network input config
UNVT_day_sched
nciDay_Sched[x]
x = 0 to 6
4 unoccupied_event_4 1439
This configuration property defines the space temperature
setpoints for various heat, cool and occupancy modes.
The stand-by setpoints can be modified but are not used by the
controller, as it does not support Stand-By occupancy mode.
Valid Range and Default values:
Sub Name Valid Range Default value
01 occupied_cool 54 to 100°F
(12 to 37.5°C)
73.5°F (23°C)
02 standby_cool
Not Used Not Used
03 unoccupied_cool 54 to 100°F
(12 to 37.5°C)
82.5°F (28°C)
04 occupied_heat 40 to 90°F
(4.5 to 32°C)
70°F (21°C)
05 standby_heat
Not Used Not Used
Temperature
Setpoints
network input config
SNVT_temp_setpt
nciSetPts
06 unoccupied_heat 40 to 90°F
(4.5 to 32°C)
61°F (16°C)
This configuration property defines the thermostat’s common
configuration parameters and their settings.
Valid Range and Default values:
Name Valid Range Default value
password 0 to 1000 0
unoccupied timer 0.5 to 24.0 hours 0.5
anticycle 0, 1, 2, 3, 4, or 5
minutes
2 minutes
power-up delay 10 to 120 sec. 10 sec.
temporary occ time 0, 1, 2, 3 to 12 hours 3 hours
heating stages cph 3, 4, 5, 6, 7 or 8 CPH 4 CPH
cooling stages cph 3 or 4 CPH 4 CPH
heat maximum
setpoint
40 to 90°F (4.5 to 32°C) 90°F
cool minimum
setpoint
54 to 100°F
(12 to 37.5°C)
54°F
oa temp heat lockout -15 to 120°F (-26 to
49°C)
120°F
oa temp cool
lockout
-40 to 95°F (-40 to
35°C)
-40°F
calib room sensor ±5°F (±2.5°C) 0°F
calib outdoor air
sensor
±5°F (±2.5°C) 0°F
Thermostat’s
common
configuration
parameters
network input
config
UNVT_cfg_1_rtu_hp
nciCfg1RtuHp
deadband 2 to 4°F with 1°F
increments (1 to 2°C)
2°F