Viconics VT7200 (Echelon) Integration Manual Manuel d'utilisateur Page 16

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 27
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 15
16
Parameter Variable Name Function
This configuration property defines the thermostat’s common
configuration parameters and their settings.
Valid Range and Default values:
Thermostat
Common
Configuration
Parameters
network input config
UNVT_cfg_1_fcu_zn
nciCfg1FcuZn
Sub Name Valid Range Default value
19 proportional band 3 to 10 F 3 F
20 aux contact config 0 = Aux Contact used
for reheat
1 = Aux NO with
occupancy
2 = Aux NC with
occupancy
3 = Aux NO with
occupancy & Fan
On
4 = Aux NC with
occupancy & Fan
On
5 = Remote control
nviAuxOut
0
21 reheat time base 0 = 15 minutes
1 = 10 seconds
0
22 fan mode 0 = Low
1 = Med
2 = High
3 = Auto
4 = On
Depending on
Fan Menu
Selected
23 auto fan 0 = Auto Speed
1 = Auto Speed and
Auto Demand
0 = Auto
Speed
24 pir stand-by timer 0.5 to 24.0 Hours 0.5 Hours
25 pir unoccupied timer 0.0 to 24.0 Hours 0.0 Hours
Vue de la page 15
1 2 ... 11 12 13 14 15 16 17 18 19 20 21 ... 26 27

Commentaires sur ces manuels

Pas de commentaire