1 | PIR Ready VT76x7 Series-Installation Guide CONTENTS Installation 2 Location 2 Installation 2 Theory of operation 3 Features overview 4
10 | PIR Ready VT76x7 Series-Installation Guide User menu flow chart: NOTE: Prompts may not all be present depending on model selected Sc h e du l
11 | PIR Ready VT76x7 Series-Installation Guide Sequence of auto-scroll status display: ROOM TEMP & RH CLOCK STATUS SYSTEM MODE SCHEDULE STATUS
12 | PIR Ready VT76x7 Series-Installation Guide Three status LEDs on the Terminal Equipment Controller cover are used to indicate the status of the f
13 | PIR Ready VT76x7 Series-Installation Guide Local keypad interface Each of the sections in the menu is accessed and configured using 5 keys on t
14 | PIR Ready VT76x7 Series-Installation Guide Occupied setpoints adjustments There is a default profile set in the Terminal Equipment Controller fr
15 | PIR Ready VT76x7 Series-Installation Guide C) Temperature setpoints Permanent setpoint changes Temperat set Y/N This menu permits the ad
16 | PIR Ready VT76x7 Series-Installation Guide 50% RH and the dehumidification setpoint is changed from 70% RH to 45% RH, the humidification setpoin
17 | PIR Ready VT76x7 Series-Installation Guide E) System mode setting Sys mode set Y/N This menu is accessed to set system mode operation Use ▲
18 | PIR Ready VT76x7 Series-Installation Guide Monday timer Schedule set Tuesday timer Schedule set Wednesday timer Schedule set Other days are ide
19 | PIR Ready VT76x7 Series-Installation Guide ** To schedule a day as occupied for 24 hours, set that day Occupied time to 12:00 AM and Unoccupied
2 | PIR Ready VT76x7 Series-Installation Guide INSTALLATION Remove the security screw on the bottom of Terminal Equipment Controller cover. Op
20 | PIR Ready VT76x7 Series-Installation Guide * Scheduling events to the same time will cancel the last period and leave the Terminal Equipment Con
21 | PIR Ready VT76x7 Series-Installation Guide Enabling a permanent occupied or permanent unoccupied schedule hold will cancel any active overrid
22 | PIR Ready VT76x7 Series-Installation Guide CONFIGURATION PARAMETERS DEFAULT VALUE SIGNIFICANCE AND ADJUSTMENTS PswrdSet Configuration parameter
23 | PIR Ready VT76x7 Series-Installation Guide Channel Channel selection Default value = 10 Range is: 10 to 26 Conditional parameter to Wireless mo
24 | PIR Ready VT76x7 Series-Installation Guide DI 1 Digital input no.1 configuration Open contact input = function not energized Closed contact inpu
25 | PIR Ready VT76x7 Series-Installation Guide Lockout Keypad lockout levels Default value = 0 No lock 0 = No lock 1 = Low level 2 = High level USER
26 | PIR Ready VT76x7 Series-Installation Guide Pband Proportional Band setting Default value 2 = 2.0 °F ( 0.6 °C ) Adjust the proportional band used
27 | PIR Ready VT76x7 Series-Installation Guide Heat cph Heating stages cycles per hour Default value = 4 C.P.H. Will set the maximum number of heat
28 | PIR Ready VT76x7 Series-Installation Guide TOccTime Default value = 3 hours Temporary occupancy time with occupied mode setpoints when override
29 | PIR Ready VT76x7 Series-Installation Guide C stage Number of cooling stages 2 stages model only Default value = 2 stages Will revert the op
3 | PIR Ready VT76x7 Series-Installation Guide 11. Gently push excess wiring back into hole (fig. 3). 12. Re-Install wiring terminals in their corr
30 | PIR Ready VT76x7 Series-Installation Guide RH LT Reset RH lower outside temperature setpoint Default value = -20°F (-29°C) Minimum outsi
31 | PIR Ready VT76x7 Series-Installation Guide RH HT Reset RH higher outside temperature setpoint Default value = 32°F (0°C) Maximum outdoor air tem
32 | PIR Ready VT76x7 Series-Installation Guide RE SP Reset humidity setpoint Default value = 20% RH The RH setpoint will be reset from the user setp
33 | PIR Ready VT76x7 Series-Installation Guide Terminal Equipment Controller will not call for heating Wrong mode selected Select heating mode Termi
34 | PIR Ready VT76x7 Series-Installation Guide HUMIDITY CONTROL Humidity reset Humidity setpoint reset by outside air temperature If an outdoor
35 | PIR Ready VT76x7 Series-Installation Guide SPECIFICATIONS Terminal Equipment Controller power requirements: Operating conditions: Storage co
36 | PIR Ready VT76x7 Series-Installation Guide DRAWING & DIMENSIONS Viconics Technologies Inc. Tel.: Fax: Toll free:www.viconics.com
4 | PIR Ready VT76x7 Series-Installation Guide Features overview 7 day schedule models, 2 or 4 events Gas/oil or electric system compatibility
5 | PIR Ready VT76x7 Series-Installation Guide MODEL CHART
6 | PIR Ready VT76x7 Series-Installation Guide Network ready All Viconics VT76x7 series Terminal Equipment Controllers are designed for stand-alon
7 | PIR Ready VT76x7 Series-Installation Guide Screw terminal arrangement Wiring notes: Note 1: If the same power source is used for the heating
8 | PIR Ready VT76x7 Series-Installation Guide TYPICAL APPLICATIONS
9 | PIR Ready VT76x7 Series-Installation Guide Remote humidity sensor accessories Model no. Description VH2020W1000 Wall mounted humidity sensor VH2